EM converterPACK ST 60 V UNV COND

SELFTEST version (US applications)

Product description

  • Emergency lighting LED driver with selftest function
  • Only for US applications
  • Battery pack enclosed
  • For self-contained emergency lighting
  • For LED modules with a forward voltage up to 57 V
  • Class 2
  • UL certified
  • EM = Emergency
  • 5 years guarantee

Properties

  • Non maintained operation
  • Self-test
  • 90 minutes rated duration
  • Compatible with most constant current LED drivers (see data sheet, LED driver compatibility)
  • 3-pole technology: 2-pole LED module changeover and delayed power switching for the LED driver
  • Automatic shutdown of output if LED load is out of range
  • Constant power output
  • Combined status display LED and test switch included
  • Electronic charge system
  • Deep discharge protection
  • Short-circuit-proof battery connection
  • Polarity reversal protection for battery
  • Self-test:
  • Status of the battery
  • Status of the LED
  • Function test
  • Duration test

Batteries

  • High-temperature cells
  • NiMH batteries
  • 5 years guarantee for NiMH batteries
Autoscroll for tables
Ordering data
Type Article number Rated du­ra­tion Packaging, carton Packaging, pallet Weight per pc. Hole spacing D Dimensions
L x W x H
EM converterPACK ST 1-9-5 60V UNV COND 28002865 1.5 h 16 pc(s). 480 pc(s). 0.90 kg 252 mm 260 x 65 x 22 mm
EM converterPACK ST 1-9-9 60V UNV COND 28002868 1.5 h 10 pc(s). 400 pc(s). 1.05 kg 299 mm 307 x 65 x 22 mm
EM converterPACK ST 1-9-15 60V UNV COND 28002871 1.5 h 10 pc(s). 400 pc(s). 1.35 kg 364 mm 372 x 65 x 22 mm
Approval marks:
UL_Listed
Technical data
Rated supply voltage 120 – 277 V
Mains frequency 50 / 60 Hz
Typ. λ 0.5C
Output current Refer to data sheet
Starting time < 0.25 s from detection of emergency event
Overvoltage protection 305 V
U-OUT (including open- / short-circuit and double load) 60 V
Max. open circuit voltage 60 V
Ambient temperature ta 0 ... +50 °C
Max. casing temperature tc 70 °C
Mains voltage changeover threshold emergency mode 30 V
Mains voltage changeover threshold mains mode 70 V
Type of protection IP20
Functional test Monthly 30 s test
Duration test Yearly 90 minutes test
Autoscroll for tables
Specific technical data
Type Mains voltage LED module forward voltage range Typ. output power P emergency Mains current in charging operation Mains power in charging operation
Initial charge Fast re­charge Trickle charge Initial charge Fast re­charge Trickle charge
EM converterPACK ST 1-9-5 60V UNV COND 120 V 13 – 57 V 5 W 40 mA 36 mA 5.1 mA 2.1 W 1.8 W 0.5 W
EM converterPACK ST 1-9-5 60V UNV COND 277 V 13 – 57 V 5 W 25 mA 22 mA 3.7 mA 2.5 W 2.0 W 0.5 W
EM converterPACK ST 1-9-9 60V UNV COND 120 V 14 – 57 V 9 W 51 mA 50 mA 5.9 mA 2.9 W 2.8 W 0.5 W
EM converterPACK ST 1-9-9 60V UNV COND 277 V 14 – 57 V 9 W 30 mA 29 mA 4.2 mA 3.2 W 2.8 W 0.6 W
EM converterPACK ST 1-9-15 60V UNV COND 120 V 15 – 57 V 15 W 62 mA 68 mA 6.9 mA 3.9 W 3.9 W 0.6 W
EM converterPACK ST 1-9-15 60V UNV COND 277 V 15 – 57 V 15 W 38 mA 39 mA 4.8 mA 4.0 W 4.0 W 0.6 W
Document Size Date  
 
EM_converterPACK_SELFTEST_60V_UNV_COND_en.pdf
Data sheet
766 KB 28/09/2022
MSDS_Tridonic_NiMH_1.5Ah_2.1Ah_3.8Ah.pdf
Safety data sheet – NiMH 1.5 Ah, 2.1 Ah, 3.8 Ah
87 KB 26/06/2020
Functional_Description_SELFTEST_Emergency_Devices_en.pdf
Functional Description SELFTEST Emergency Devices
677 KB 25/11/2020
Certificates / declarations of conformity
Type      Article number      Certificates     
Certificates ()
Autoscroll for tables
CAD / RAY
Type Article number CAD Files
EM converterPACK ST 1-9-5 60V UNV COND 28002865 CAD (15.4 MB)
EM converterPACK ST 1-9-9 60V UNV COND 28002868 CAD (15.6 MB)
EM converterPACK ST 1-9-15 60V UNV COND 28002871 CAD (15.7 MB)
 
 
Visiting from the US or Canada?
Go to our dedicated site.
http://www.tridonic.us or stay on tridonic.com